Toyopuc Error Codes
Error code (Decimal) |
Error code (Hex) |
Meaning |
---|---|---|
0 | 0x000 | No Error |
17 | 0x011 | Inability to process data because of faulty CPU Module Hardware |
32 | 0x020 | Fixed Data (ENQ) within relay command is not 05. |
33 | 0x021 | Faulty transfer number |
35 | 0x023 | Erroneous command code |
36 | 0x024 | Erroneous subcommand code |
37 | 0x025 | Erroneous command-format byte |
38 | 0x026 | Erroneous function call operand number |
49 | 0x031 | Write of function call prohibited by sequence operation |
50 | 0x032 | A command that is defeated during a stop continuity is activated during a stop continuity |
51 | 0x033 | Attempting to execute a debug function despite non debug mode |
52 | 0x034 | Access prohibited due to configruation |
53 | 0x035 | Non-executable due to configuration |
54 | 0x036 | Non-executable due to other device configuration |
57 | 0x039 | Attempting to start scanning without any reset afterwrting I/O point number parameters |
60 | 0x03C | During a fatal failure a command has issued that is not executable during a fatal failure |
61 | 0x03D | Non-executable due to competing process with a different-factor command is executed |
62 | 0x03E | Non-executable command due to reset existence |
63 | 0x03F | Non-exectuable command due to stop duration |
64 | 0x040 | Address of a reading/writing command or address + data number of a command is out of range |
65 | 0x041 | Word/byte number is out of range |
66 | 0x042 | Non-designated data is sent |
67 | 0x043 | Erroneous function-call operand |
82 | 0x052 | Though any timer or counter is employed a command for reading.writing the set/recent values is issued. |
102 | 0x066 | No reply is sent from link module with the link exchange number specified by a relay command |
112 | 0x070 | Non-executable module with the link exchange number specified by a relay command |
114 | 0x072 | No reply is sent from link module with the link exchange number specified by a relay command |
115 | 0x073 | Multiple relay commands were issued to the same link module |
512 | 0x200 | Timed Out Waiting for Response from Remote |
513 | 0x201 | Timed Out Waiting for Echoed Message |
514 | 0x202 | Unexpected Device Response |
515 | 0x203 | Mismatch Response Command Code |
516 | 0x204 | Relay Command: Exchange Number Mismatch |
517 | 0x205 | Relay Command: Wrong Number of Hops |
768 | 0x300 | No Error |
769 | 0x301 | Port Not Defined |
770 | 0x302 | Port Failed To Connect |
771 | 0x303 | Port Lost Connection |
772 | 0x304 | Serial Port Settings Out of Range |
773 | 0x305 | Serial Port Already In Use or Not Available |
774 | 0x306 | Serial Port Access Denied |
775 | 0x307 | Serial Port General Failure |
776 | 0x308 | Serial Port Invalid Parameter |
777 | 0x309 | Port Not Connected |
784 | 0x310 | Port Unknown Error |