EventDatabaseName
Configure events to be logged in a specific database by setting the "EventDatabaseName" property in Advanced Properties.
The value must be the name of a valid Alarm Database Tags that events will be logged to. Otherwise, if a name is not specified, the tag does not exist or the tag is invalid, events will continue to be logged to the default System Event Database.
Events will be logged to the next available Alarm Database tag if the System Event Database is disabled and "EventDatabaseName" is not set (stores an 'Invalid' value). If there is no available Alarm Database tag while these conditions are met, no events specific to the workstation will be logged and no alarms will be displayed or sounded.
The name must include the path to the Database tag from the root of the tag hierarchy. For example, "EventDatabaseName = "Plant\Databases\CustomEventDatabaseTagName".
Section: System
Default: EventDatabaseName = Invalid
*No restart required (Settings.Dynamic property)